Power factor correction capacitors
Calculate the kvar of capacitors needed to raise the power factor and the capacitance per phase in µF. The reactive power to compensate is Qc = P·(tan φ1 − tan φ2). The calculator is free and shows the formula, the working and a numerical example, with no sign-up.
Results
⚠️ Indicative electrical calculation, NOT a design: cable section, ampacity and voltage drop must be verified by a qualified technician under IEC/EN, NEC and local regulations before any installation. Legal notice
Step-by-step calculation with your values
Formulas
\tan\varphi_1 = \tan(\arccos(\cos\varphi_1))\tan\varphi_2 = \tan(\arccos(\cos\varphi_2))Q_c = P \cdot (\tan\varphi_1 - \tan\varphi_2)C = \frac{Q_c}{2\pi f \cdot V^2}How it is calculated
The reactive power to compensate is Qc = P·(tan φ1 − tan φ2). For a star-connected three-phase bank the capacitance per phase is C = Qc / (2π·f·V²), V being the line voltage.
Results are indicative: for real projects and installations always check applicable standards and a qualified professional.
Example
With the values: Active power = 50 kW; Current cos φ = 0.75; Target cos φ = 0.95; Voltage = 400 V; Frequency = 50 Hz — you get:
- Current tan φ: 0.88192
- Target tan φ: 0.32868
- Capacitor reactive power: 27.662 kvar
- Capacitance per phase (star): 550.31 µF
Frequently asked questions
Which formula does the “Power factor correction capacitors” calculator use?
The reactive power to compensate is Qc = P·(tan φ1 − tan φ2). For a star-connected three-phase bank the capacitance per phase is C = Qc / (2π·f·V²), V being the line voltage.
Is FunConvert free?
Yes. Every converter and calculator is free, with no sign-up and nothing to install. Calculations run in your browser.