Power factor correction capacitors

Calculate the kvar of capacitors needed to raise the power factor and the capacitance per phase in µF. The reactive power to compensate is Qc = P·(tan φ1 − tan φ2). The calculator is free and shows the formula, the working and a numerical example, with no sign-up.

Results

⚠️ Indicative electrical calculation, NOT a design: cable section, ampacity and voltage drop must be verified by a qualified technician under IEC/EN, NEC and local regulations before any installation. Legal notice

Step-by-step calculation with your values

    Formulas

    \tan\varphi_1 = \tan(\arccos(\cos\varphi_1))
    \tan\varphi_2 = \tan(\arccos(\cos\varphi_2))
    Q_c = P \cdot (\tan\varphi_1 - \tan\varphi_2)
    C = \frac{Q_c}{2\pi f \cdot V^2}

    How it is calculated

    The reactive power to compensate is Qc = P·(tan φ1 − tan φ2). For a star-connected three-phase bank the capacitance per phase is C = Qc / (2π·f·V²), V being the line voltage.

    Results are indicative: for real projects and installations always check applicable standards and a qualified professional.

    Example

    With the values: Active power = 50 kW; Current cos φ = 0.75; Target cos φ = 0.95; Voltage = 400 V; Frequency = 50 Hz — you get:

    • Current tan φ: 0.88192
    • Target tan φ: 0.32868
    • Capacitor reactive power: 27.662 kvar
    • Capacitance per phase (star): 550.31 µF

    Frequently asked questions

    Which formula does the “Power factor correction capacitors” calculator use?

    The reactive power to compensate is Qc = P·(tan φ1 − tan φ2). For a star-connected three-phase bank the capacitance per phase is C = Qc / (2π·f·V²), V being the line voltage.

    Is FunConvert free?

    Yes. Every converter and calculator is free, with no sign-up and nothing to install. Calculations run in your browser.